0

TOA FV-2148W-AS

Contact

The FV-2148W-AS is a compact wall-mounted evacuation announcement system. It is designed for both general announcements and evacuation announcements. The system can be mounted on the wall with 4 evacuation announcements available, a total output power of up to 480W and 10 Zones, supporting up to 4 remote microphones. The FV-2148W-AS can be connected to a fire alarm system, and broadcasts the announcement automatically when it receives an activation signal.

The optional MP-300 module allows background music to be played when needed.

Description

Specifications:

Model FV-2148W

Power supply 100 – 240 V AC ~ 50/60 Hz, M4 screw type

Power consumption
99 W (EN 62368-1)
530 W (at rated output)

Speaker output power 480 W

Inputs
Front microphone: -60 dB*, 2.2 KΩ, unbalanced, XLR connector
Input 1: -60 dB*/-20dB* (selectable), 2.2 KΩ, balanced, screw type
Socket jack priority input (if connected to a 6mm jack, the audio will be automatically selected and the screw type will be muted)
Input 2: -20 dB*, 10 KΩ, balanced, screw type

Remote zone microphone Number of remote zone microphones usable: RM-200M max. max 4 sets, RJ45 cable and max length 800m

Outputs
Speaker output: screw type
Speaker zone selector: 10 zones, high impedance (100V line) per zone or group of zones

S/N ratio over 60 dB

Total noise Below 1 % at 1 kHz, 1/3 output power

Frequency response 50 Hz – 20000 Hz

Tone adjustment Bass: ± 10 dB at 100 Hz Treble: ± 10 dB at 10 kHz

Emergency announcement
Alert, Evacuation, False, Clear
(Continuous/One-time repeat – selectable)

Chime 2 chime

Input control
FA IN: no-voltage to make input, open voltage: 24 V DC, short circuit current: below 5mA, screw type
CTRL IN 1 – 6: no-voltage to create input, open voltage: 24 V DC, short circuit current: under 5mA, screw type (can be attached)

Output control
FA OUT: Relay type, voltage: 24 V DC, screw type
CTRL OUT 1 – 2: Relay type, voltage: 24 V DC, screw type (can be assigned)

Indicator light
Power indicator, signal indicator, over-peak signal indicator, error indicator
Indicator for each speaker zone, speaker zone group
Status indicator light: Alert, Evacuation, False, Clear

Operating temperature 0 ·c to +40 ·c

Allowable humidity Below 90 % RH (no condensation)

Cooling Fan-cooled

Components Steel plate, black paint

Dimensions 370 (W) x 456 (H) x 132 (D) mm

Weight 9.1 kg

Components Front microphone, sample paper

Accessories option MP-300