The VX-3004F is a 4-zone AB loudspeaker controller in TOA’s VX-3000 series of voice evacuation systems. The device complies with the European EN54 standard for fire alarm systems. The device is equipped with audio inputs and can be directly connected to speaker outputs when used with amplifier modules. The device can also be set to broadcast a warning message with a higher priority than the normal warning level. Two emergency states can be activated at the same time (Fire zone evacuates, neighboring zones issue warnings). With the network connection feature, the system can be distributed.

The device includes the following features: Digital processing function allows to adjust the sound of each separate input and each output zone, anti-feedback function helps to reduce howling in the PA system, VOX is a function that allows START/STOP through the input audio signal, ANC function allows to adjust the system sound according to the environmental noise. (ANC function can distinguish the output sound of the device and the surrounding noise. The output sound of the device is not considered noise). The indicator light shows the error status and the status of each amplifier on the integrator.

The device has 4 outputs available, with one output providing both A and B ports for connecting to speaker wires. Supports up to 4 Power Amplifier Modules mounted in the integrator. With 4 amplifier channels, we can use them as 4 separate speaker outputs or use 3 separate speaker outputs and 1 as a spare. The VX-3004F is equipped with input and output ports for backup amplifiers, so the device can easily share backup amplifiers with other VX-3000F sets.

Description

Specifications:

Power supply 20 – 33 V DC, removable connector (4 pins)

Power consumption 24 W (frame only) at 33 V DC input, 90 W (RS Link: 2 A output) at 33 V DC input

Indicators POWER (green) x1, RUN (green) x 1, EMERGENCY (red) x 1, CPU OFF (red) x 1, LAN A (green) x 1, LAN B (green) x 1, RS LINK A (green) x1, RS LINK B (green) x 1
Error status (yellow)
GENERAL x 1, UNIT x 1, NETWORK x 1, EMG MIC x 1, FUSE x 1, POWER x 1, CPU x 1, ZONE x 8
Audio gain
PEAK (red) x 4, SIGNAL (green) leaf) x 4, OPERATE (green) x 4, POWER (green) x 4

Operation
Error control switch x 2 (ACK/RESET)
Test switch x 1 (LAMP TEST)
Setting switch: ID NO., RESET, IMPEDANCE, setting (front panel)

LAN A, B
Number of connection ports: 2 (LAN A, LAN B)
Network I/F: 100BASE-TX
Network protocol: TCP, UDP, ARP, ICMP, RTP, IGMP, FTP, HTTP, NTP
STP protocol: RSTP
Audio transmission system: TOA audio packetization (*1)
Audio encoding method: PCM
Sampling frequency: 48 kHz
Audio quantification bits: 16 bits
Connected equipment: other VX-3004F, VX-3008F, VX-3016F, NX-300, VX-3000PM, VX-3000CT, Switching HUB
Connection port: RJ45
Connection cable: CAT5 or higher twisted pair cable
Number of cascades: up to 7
Maximum cable distance: 100 m

RS Link A, B
Number of connection ports: 2 (RS LINK A, RS LINK B)
Audio input level: 0 dB (*2)
Power: up to 1 A per port
Connection port: RJ45
Connection cable: CAT5-STP or higher shielded twisted pair cable
Maximum cable distance: 1200 m

DS Link
Connection device:
DS LINK of power supply device
Connection port: RJ45
Connection cable: CAT5-STP or higher shielded twisted pair cable
Maximum cable distance: 5m

Analog Link
Number of connection ports: 1 input, 1 output
Connecting device: other VX-3004F, VX-3008F, VX-3016F
Connecting port: RJ45
Connecting cable: anti-interference twisted pair cable CAT5-STP or higher
Maximum cable distance: 800 m

Control input 1, 2
16 inputs, no-voltage input, open voltage: 24 V DC, short-circuit current: 2 mA
Fault detection system: short circuit, open circuit, method: voltage detection
Connecting port: RJ45
Connecting cable: anti-interference twisted pair cable CAT5-STP or higher

Emergency control input
Input 2: isolated voltage input, -24 to +24 V
Connecting port: RJ45
Connecting cable: anti-interference twisted pair cable CAT5 or higher up

VOX function
Threshold: -60 to 0 dB (1 dB steps)
Delay: 0 to +10 dB, hold time: 10 ms – 10 s
Can be set for each audio input

Control output 1, 2
Common output: 8 with control output 1
Individual output: 3 with control output 2
COMMON FAULT, CPU FAULT, CPU OFF
Dry contact, electromagnetic contact output, control current: 10 mA, operating voltage: 28 V DC
Connection port: RJ45
Connection cable: CAT5-STP or higher shielded twisted pair cable

ATT/control output
8 outputs, dry contact, relay contact (NC, NO, C), control current: 2 mA to 5 A, operating voltage: 125 V AC, 40 V DC
Connection port: removable connector (12 pins) x 2

Audio input 1, 2, 3, 4
4 inputs
Sound intensity:
LINE: -20 dB (*2), MIC: -60 dB (*2)
LINE/MIC/ANC sensor (changeable by software setting)
Gain control: adjustable volume (on front panel)
– ∞ to 0 dB
Input impedance: 47 kΩ, electromagnetically balanced
Frequency response: 40 Hz – 20 kHz ±1 dB (at DA CONTROL LINK, 0 dB output)
Distortion: 1% or less (at DA CONTROL LINK, 0 dB output, 1 kHz)
S/N ratio: 60 dB or more (at DA CONTROL LINK, A-weighted)
Phantom power: 24 V DC, configurable by software
Connection terminals: removable connector (6 pins) x 2

Digital signal processing

7-point feedback suppression (automatic), configurable for each audio input and RS LINK (A/B)

Equalizer/Filter
3 frequency bands for each audio input and RS LINK (A/B), 6 frequency bands for each gain output
Equalizer parameters: 20 Hz – 20 kHz, ±15 dB, Q: 0.267 – 69.249
Filters: high-pass filter 20 Hz – 20 kHz, 6 dB/oct, 12 dB/oct
low-pass filter 20 Hz – 20 kHz, 6 dB/oct, 12 dB/oct
multi-pass high-pass filter 6 – 20 kHz, ±15 dB
multi-pass low-pass filter 20 – 500 Hz, ±15 dB
Notch band-stop filter (gain output only) 20 Hz – 20 kHz, Q: 8.651 – 69.249
all-pass filter (gain output only) 20 Hz – 20 kHz, Q: 0.267 – 69.249
Horn equalizer (only for gain output) 20 kHz, 0 to +18 dB (0.5 dB steps)

Compressor
Threshold: -20 to 0 dB (1 dB steps)
Ratio: 1:1, 1.1:1, 1.2:1, 1.3:1, 1.5:1, 1.7:1, 2:1, 2.3:1, 2.6:1, 3:1, 4:1, 5:1, 7:1, 8:1, 10:1, 12:1, 20:1, ∞:1
Attack time: 0.2 ms – 5 s, Release time: 10 ms – 5 s
Gain: – ∞ to +10 dB, Knee type: hard knee, middle knee, soft knee

Delay For each gain output, 0 – 2730 ms (0.021 ms steps)

ANC(environmental noise control)
Gain output level control, automatic sensor input reference level measurement, sensor input reference level adjustment
Maximum output signal level control: -15 to 0 dB
Minimum output signal level control: -18 to -3 dB
Sample time setting: 10 s, 20 s, 30 s, 1 min, 5 min
Gain ratio setting: (environmental noise: output signal level) 6:3, 5:3, 4:3, 3:3, 3:4, 3:5, 3:6
Environmental noise measurement frequency setting: 20 Hz – 20 kHz, 3 point

Time programming
Weekly setting method
Daily setting: 50 scenarios, 10 types
Holiday setting: 50 types

Time adjustment Control input, NTP

Speaker line
4 channels (with A/B LINE speaker output), 1 ground connector
Maximum current/voltage: 100 Vrms, 5 Arms
Connection terminal: removable connector (17 pins) x 1
Fault detection system: short circuit, open circuit, ground fault,
method: impedance or end of line

Backup amplifier input/output
Input: 1, output: 1
Maximum current/voltage: 100 Vrms, 5 Arms
Connection terminal: removable connector (2 pins) x 2

Module (*3)
Number of modules: 4
DA CONTROL LINK x 4
DA OUTPUT LINK x 4 (only when installing a power amplifier module)

Environment -5 ℃ to +45 ℃

Environment 90 %RH or less (non-condensing)

Materials Enclosure: Stainless steel plate, 30 % gloss black paint

Dimensions 483 (W) × 132.6 (H) × 345 (D) mm

Weight 7.6 kg

Accessories Rack mount (pre-installed on the device) x 2, Rack mount screws x 4, CD (installation software) x 1, Removable connector (2 pins) x 2, Removable connector (4 pins) x 1, Removable connector (6 pins) x 2, Removable connector (12 pins) x 2, Removable connector (17 pins) x 1, Ferrite clip x 2