TOA VX-050DA
Contact
The VX-050DA is a 500W digital amplifier module used in the VX-3000 system. It complies with the European EN54 standard for fire alarm systems. The module is a 1-channel class-D digital amplifier module that saves power and is lightweight.
The VX-050DA can be set to operate in standby mode to reduce power consumption. The module requires the use of a dedicated controller VX-3004F, VX-3008F, VX-3016F and an emergency power supply VX-3000DS or VX-3150DS.
Description
Specifications:
Power supply
31 V DC (Operating range: 20 – 33 V DC)
DC power supply: M4 port, distance between baffles: 11 mm
Amplifier system Class D
Power consumption
1.3 W (standby), 16 W (no audio input connected)
100 W (1/8 rated output), 590 W (rated output)
at 31 V DC, output voltage selection: 100 V
Rated output power
500 W (at 100 V line and minimum impedance, maximum load)
350 W (at 70 V line and minimum impedance, maximum load)
250 W (at 50 V line and minimum impedance, maximum load)
(at AC Mains VX-3000DS or VX-3150DS: 187 – 253 V)
Output voltage 100 V (70 V, 50 V: selectable)
Minimum impedance 20 Ω (at 100 V line), 14 Ω (at 70 V line), 10 Ω (at 50 V line)
Maximum load 0.5 μF
Number of channels 1
DA CONTROL LINK input: Nylon connector (15 pins)
DA OUTPUT LINK output: Nylon connector (2 pins)
Frequency response 40 Hz – 20 kHz: -5 to +1 dB (at 100 V line, rated output 30 dB (*1))
Distortion 1 % or less (at 100V line, rated output, 1 kHz)
S/N ratio 100 dB or more (at 100 V line, A-weighted)
Operating temperature -5 ℃ at +45 ℃
Allowable humidity 90 %RH or less (non-condensing)
Material Surface treated steel plate
Dimensions 82.8 (W) × 91 (H) × 358.2 (D) mm
Weight 1.4 kg
Accessories DA CONTROL LINK cable x1, DA OUTPUT LINK cable x1, DC FUSE (30 A) x1